Daikin Non Inverter 8-Way Cassette FCC-AV1S

Daikin FCC-AV1S is a non-inverter ceiling cassette with eight-way airflow. AirHub360 groups it under 4way Cassette for comparison with other four-sided ceiling cassette formats.

Models and technical specifications ↓Discuss this series ↗

What to know about this series

  • R32 refrigerant and a built-in drain pump
  • LED-equipped panel is an optional accessory

Plan around the installation site

Compare installation cost and operating hours with an inverter option. Check all eight air paths for nearby walls or shelving that may obstruct distribution.

DAIKIN / MODEL DATA

Models and technical specifications

Select a code to view its specifications, and confirm the indoor/outdoor pairing before using the data for design.

FCC18AV1S / RC18AV1S
SpecificationUnitManufacturer data
System data
System model combination—FCC18AV1S / RC18AV1S
Cooling capacitykW5.4
Cooling capacityBTU/hr18,500
Power inputW1,620
Power supplyV/Ph/HzSupply from Outdoor220V / 1 Phase / 50Hz
Indoor unit
Indoor unit model—FCC18AV1S
Fan speed settings—4 Steps
Air filter—Anti-Virus Filter
Airflow ratem3/min25/21/17/13
Airflow ratecfm890/760/620/490
Sound leveldB(A)44/40/37/35
Dimensions (H × W × D)mm246 X 840 X 840
Weightkg22
Drain connection sizemm19.00
Decorative panel dimensions (H × W × D)mm69 x 950 x 950
Decorative panel weightkg5
Outdoor unit
Outdoor unit model—RC18AV1S
Sound leveldB(A)52
Dimensions (H × W × D)mm615 x 845 x 300
Weightkg42
Liquid refrigerant pipe sizemm/inch/HunØ6.4 mm
Gas refrigerant pipe sizemm/inch/HunØ12.7 mm
Outdoor heat exchanger type—Fin tube(Copper)
Compressor type—Rotary type
Compressor motor outputW1,364
Maximum piping lengthm35
Maximum height differencem20
Refrigerant—R32
Piping length without additional refrigerantm7.5
Factory refrigerant chargekg1.1

Specifications apply to the selected model. Noise and airflow can vary with operating settings. Compare efficiency figures under equivalent test conditions. Matching cooling capacity alone does not establish suitability for replacing an existing unit.

Daikin Sky Air questions, answered

Is FCC-AV1S an inverter model, and is the LED panel included?

This is a non-inverter series. The LED panel is optional and should be listed separately in the quotation rather than assumed to be included.

How should cooling capacity be selected?

Calculate the heat load from room size, height, sunlight, occupancy and equipment. AirHub360 can then help check the model, power supply and outdoor-unit location.

AIRHUB360 / LET’S PLAN TOGETHER

Discuss this series

Start with ceiling height, available ceiling void, equipment position and airflow direction. Then assess heat load, electrical supply, refrigerant and drain routes, and maintenance access. Our 4-way cassette family includes Round Flow for easier comparison of installation formats. Round Flow distributes air through 360 degrees, rather than just four directions.

Discuss this series ↗
← All Sky Air

LET’S TALK ABOUT YOUR SPACE

Start with comfort that fits you.

Tell us about your space and what you need. The AirHub360 team can help you plan the next step.

Talk to AirHub360
LINE CHAT